Loading
Back to
View All
  • Products
    • ALL PRODUCTS
      • Contactors
      • Overload Protection
      • Starters + Enclosed Product
      • Motor Controllers + MCCBs
      • Softstarters
      • Circuit Protection
      • Disconnect Switches
      • Rotary Cam Switches
      • Control + Timing Relays
      • Pilot Devices
      • Terminals
      • Signaling Devices
      • Power Supplies
      • Infinitum Motors
    • Custom Control Panels
      • Combination Starters
      • Explosion Proof
      • Multi-Speed and Reduced Voltage
  • Library
    • LIBRARY
      • Product Catalog
      • Literature
      • Cross Reference
      • Technical Tips & FAQs
      • CAD Drawings
      • Wiring Diagrams
    • APPROVALS
      • UL/CSA Documents
      • CE-DOC
      • Atex
      • CCC
      • RCM/TUV/ABS/RINA
      • ISO9001
      • SUVA Certificates
      • Functional Safety Data
      • Environmental Compliance
    • Training
      • SSU
  • Company
    • COMPANY
      • About Sprecher + Schuh
      • Contact Us
      • Industries Served
      • Success Stories
      • Terms & Conditions
      • Privacy Policy
      • Technical Support
      • International
  • Sales
    • SALES
      • Find a Reseller or Sales Rep
      • Become a Distributor
      • B2B Portal
    • CONTACT US
      • United States
      • Canada
      • International
  • Support
    • SUPPORT
      • Technical Support
      • Technical Tips & FAQs
      • Find a Reseller or Sales Rep
      • Contact Us
      • B2B Portal
      • SSU
Categories
    • Overview
    • link 1
    • link 1
    • link 2
    • link 2
  • Featured
  • Privacy Policy
  • Contact Us
  • Technical Support
 

H1 Content

 

Question:

Can I swap coils from AC to DC (or vice versa) within the same contactor?

 
a

For Sizes CA7-9…55 Contactors, NO!

The CA7-9...55 Contactors cannot be converted from an AC - and, it cannot be converted from a DC to an AC coil. This is because the coil armatures used with the AC and DC coils are different.

 
a

For Sizes CA7-60…97 Contactors, Yes!

The CA7-60…97 Contactors can be converted from an AC coil to a DC coil (or DC to AC) in the field by ordering the repair coil part numbers listed in  Sprecher+Schuh catalog.

 
a

Related Links

link 1
link 2
 

Question:

What are the fuse mounting torque requirements for the L11 fusible disconnects 100A to 800A?

Answer:

The L11-J100-1753 disconnect switch is shipped with bolts already installed on the fuses terminals.

The CA7-9...55 Contactors cannot be converted from an AC - and, it cannot be converted from a DC to an AC coil. This is because the coil armatures used with the AC and DC coils are different.

 
L11 Catalog Number Fuse mounting Torque requirements Wrench Size (MM)
Row 1
Row 2 Row 2 Row 2
a

Related Links

link 1
link 2
 

Question:

  • Can you use a 3 pole L9 breaker on a 1 or 2 pole load?
  • Can you use a 3 pole L8 breaker on a 1 or 2 pole load?
  • Can I use just 2 of 3 poles from L9-10/3/C (2 phases from 3phase lines) 1st and second pole?

Answer:

You can use a 3 pole device on a 1 or 2 pole load or a 2 pole device on a 1 pole load but the following should be noted:

  • This will not affect the short circuit tripping functionality of the device.
  • This will affect the thermal calibration of the device. The device is calibrated with power on all of the available poles. Not having all the poles powered will result in less heat in the breaker. This lower heat level will result in the pole(s) being used to allow for higher current levels (more heat) before thermally tripping
  • A 3 pole device will not have the DC ratings that many of the 1 or 2 pole devices may have. If the 1 or 2 pole version of the 3 pole device is rated for DC, the poles in the 3-phase device can be used on the same voltage DC loads, but will not be labeled with any DC voltages.
 